I. COMBINATION GAS VALVE
The 24 VAC combination gas valve serves three (3)
functions: (1) manual gas shut-off, (2) main gas
flame pressure regulator, (3) automatic electric
redundant (double seated) gas shut off. (See
Figure 11)
The correct operating manifold orifice pressure range
for both natural and propane gas is 2.0” W.C.
(498.2Pa) minimum to 4.0” W.C. (996.4Pa)
maximum. By adjusting the pressure regulator
between 2.0” W.C. (498.2Pa) and 4.0” W.C.
(996.4Pa) on either natural or propane gas, a wide
input range can be achieved with a single orifice size.
If the desired input rating cannot be obtained within
the above manifold orifice pressure adjustment
range, the next size larger or smaller orifice should be
used. (Refer to orifice chart Fig. 10.)
J. PRESSURE REGULATOR ADJUSTMENT
The combination gas valve pressure regulator,
which has an outlet pressure setting range of
approximately 2.0” W.C. (498.2Pa) to 4.0” W.C.
(996.4Pa) is factory set at 3.5” W.C (871.85Pa).
When pressure adjustment is required for setting
input capacity with a selected orifice from Figure 10,
remove the regulator cap for access to the slotted
adjustment screw. Turning the screw counter
clockwise reduces manifold orifice pressure,
clockwise increases the pressure.
NOTE: MANIFOLD PRESSURE ADJUSTMENTS
CAN ONLY BE MADE WITH THE
BURNER RUNNING AND THE GAS ON.
The 1/8” (3.175mm) NPT pressure tap for orifice
manifold pressure measurement is located on the
outlet side of the combination gas valve. Use a “u”
tube manometer or dial type pressure gauge,
scaled from “0” zero to 15.0” W.C. (3736.5Pa) to
read pressure (See Figure 11).
Figure 11
1/8” (3.175mm) NPT
PRESSURE TAP
PLUG
1/8” (3.175mm) NPT
PRESSURE TAP PLUG
HSG 200/400 GAS VALVE
HONEYWELL VR8305